Fire Protection Plumbing Quick Reference Guide Fire Safety & Sprinkler System Design Summary

Essential Points: Fire Risk Analysis & Sprinkler System Design

1. Risk Analysis Summary

2. Sprinkler System Classification & Basics

3. Key Design Parameters & Criteria

ParameterSpecificationStandard Reference
Max spacing between sprinklers4m x 4m gridBS EN 12845, Table 19
Max area coverage per sprinkler12 m²BS EN 12845, Table 19
Min spacing between sprinklers2mBS EN 12845, Clause 12.3
Design Density5 mm/min (5 l/min/m²)BS EN 12845, Table 3
Assumed Max Area of Operation (AMAO)216 m²BS EN 12845, Clause 13.4.3.1
Min sprinkler discharge pressure0.35 barBS EN 12845, Clause 13.4.4
Min distance from walls102 mmNFPA 13:2002, Clause 8.6.3.3

4. Sprinkler Characteristics

Critical Design Consideration: Concealed Spaces

Voids above ceiling (>0.8m height) require sprinkler protection. Classified as Ordinary Hazard 1 (OH1).

5. Zoning & Control

6. Pipe Sizing Methodology