Hydraulic design methodology for fire sprinkler system compliant with BS EN 12845
Technical Document
August 2023
The static pressure difference between two points in the pipework is calculated using the fundamental fluid statics equation:
Where:
p = Pressure (Pa)
h = Height difference (m)
ρ = Density of water (1000 kg/m³)
g = Gravitational acceleration (9.81 m/s²)
This simplifies to a practical engineering formula:
Design Assumptions:
Critical Calculation: The highest static head occurs at the 6th floor:
A key engineering concept applied in this design is the static head gain for secondary design points at lower elevations.
This gain represents available pressure that can be "consumed" as additional frictional losses in pipe sizing calculations for lower floors.
Example: Static head gain for LL3:
This approach allows for smaller pipe diameters on lower floors while maintaining adequate pressure throughout the system.
Frictional pressure losses are calculated using the Hazen-Williams formula:
Where:
p = Pipe frictional loss (bar)
C = Pipe roughness coefficient (120 for galvanized steel)
d = Mean internal diameter of pipe (mm)
L = Equivalent length of pipe and fittings (m)
Q = Flow rate (L/min)
This is simplified to:
Where k is a constant for pipe size, type, and condition.
| Nominal Diameter (mm) | k Value | Standard Reference |
|---|---|---|
| 25 | 1.22 × 10⁻⁵ | BS 5306-2:1990, Table 36 |
| 32 | 2.93 × 10⁻⁶ | |
| 40 | 1.33 × 10⁻⁶ | |
| 50 | 4.09 × 10⁻⁷ | |
| 65 | 1.11 × 10⁻⁷ | |
| 80 | 4.97 × 10⁻⁸ | |
| 100 | 1.35 × 10⁻⁸ | |
| 150 | 1.91 × 10⁻⁹ |
Pressure losses through fittings are calculated using equivalent lengths of straight pipe.
| Nominal Diameter (mm) | 90° Elbow (m) | Tee/Cross (Branch Flow) (m) | Gate Valve (m) | Standard Reference |
|---|---|---|---|---|
| 65 | 1.89 | 3.81 | 0.51 | BS 5306-2:1990, Table 37 |
| 80 | 2.37 | 4.75 | 0.63 | |
| 100 | 3.04 | 6.10 | 0.81 | |
| 150 | 4.30 | 8.61 | 1.13 |
The fundamental design criterion for pipes upstream of the most remote design point:
Standard: BS EN 12845, Clauses 13.3.4.2 and 13.3.4.3
This ensures adequate pressure is available at all design points while optimizing pipe sizes.
The design follows an iterative process:
Example from 6th Floor Calculation:
The design employs a strategic approach to pipe sizing:
This approach efficiently utilizes the available static head gain on lower floors to reduce pipe sizes while maintaining system performance.
| Floor Level | Main Distribution Pipe Diameter | Zone Subsidiary Stop Valve Diameter |
|---|---|---|
| LL3 to 2F | 80mm | 80mm |
| 3F to 4F | 100mm | 100mm |
| 5F to 6F | 150mm | 150mm |
The complex iterative calculations were implemented using MS Excel with:
This approach provided flexibility to accommodate design changes and ensured accuracy in calculations.
The final design was verified against the criterion for all design points:
| Floor | Design Point | Frictional Loss (bar) | Static Head Gain (bar) | Difference (bar) | Compliance |
|---|---|---|---|---|---|
| LL3 | V | 4.755 | 4.361 | 0.394 | ✓ Compliant |
| 6F | B | 0.487 | 0.000 | 0.487 | ✓ Compliant |
| 3F | G | 1.905 | 1.442 | 0.463 | ✓ Compliant |
All design points show compliance with the requirement that the difference does not exceed 0.5 bar.
The hydraulic design successfully achieves: