This proposal outlines the design and implementation of a make-up water system for cooling towers at [Facility Name/Location]. The system will ensure optimal water quality and quantity to maintain cooling tower efficiency while minimizing water consumption and treatment costs.
| Component | Purpose | Design Considerations |
|---|---|---|
| Filtration System | Remove suspended solids | Multi-media filters, cartridge filters, or membrane filtration based on water quality |
| Softening System | Reduce hardness | Ion exchange or chemical softening, capacity based on hardness levels |
| Chemical Injection | Scale/corrosion control | Dosing pumps for scale inhibitors, biocides, pH adjusters |
| Reverse Osmosis | For high TDS water | Required when cycles of concentration demand very low make-up water TDS |
| Storage Tanks | Buffer capacity | Minimum 24 hours of make-up water demand |
Evaporation Loss (E): E = Q × ΔT × 0.00085 (for °F) or E = Q × ΔT × 0.00153 (for °C)
Blowdown (B): B = E/(C-1), where C = cycles of concentration
Make-up Water (M): M = E + B + D (where D = drift loss)
Cycles of Concentration: C = Make-up TDS / Blowdown TDS
| Item | Quantity | Unit Cost | Total Cost |
|---|---|---|---|
| Filtration System | 1 | [X] | [X] |
| Softening System | 1 | [X] | [X] |
| Chemical Dosing System | 3 | [X] | [X] |
| Storage Tanks | 2 | [X] | [X] |
| Piping and Valves | 1 lot | [X] | [X] |
| Total | [Total Amount] | ||