HVAC Psychrometric Chart Practice Questions Cooling & Dehumidification Psychrometrics

Cooling & Dehumidification Psychrometrics

1. Key Process on Psychrometric Chart

Process Direction: Moves left and downward from initial condition

Critical Points:

2. Performance Parameters

Sensible Heat Factor (SHF) = Qsensible / (Qsensible + Qlatent)
Parameter Ideal Range Calculation
Bypass Factor (BF) 0.1-0.3 BF = (Tout - TADP) / (Tin - TADP)
Contact Factor 0.7-0.9 CF = 1 - BF
Dehumidification Efficiency 60-85% η = (Win - Wout) / (Win - WADP)

3. Design Conditions

Application DBT (°C) RH (%) SHF Range
Comfort Cooling 24-26 45-55 0.75-0.85
Data Centers 21-23 40-50 0.90-0.95
Industrial Drying 35-40 30-40 0.50-0.65

4. Equipment Selection Guide

ΔT (DBT) ΔW (kg/kg) Recommended System
5-8°C <0.003 DX Cooling Only
8-12°C 0.003-0.006 Chilled Water + Reheat
12-15°C >0.006 Dedicated Dehumidifier

5. Troubleshooting Chart

Symptom Psychrometric Cause Solution
High RH but correct temp Process line too horizontal (high BF) Increase coil rows or reduce airflow
Low RH but cold air Process line too steep (low SHF) Add reheat or reduce dehumidification
Inconsistent conditions Unstable ADP position Check refrigerant charge/water flow