| Application | Air Velocity (fpm) | ΔT (°F) |
|---|---|---|
| Residential | 500-700 | 18-22 |
| Commercial | 800-1200 | 20-25 |
| Industrial | 1200-1800 | 25-30 |
Throw calculation: 50-75% of terminal velocity at design flow
| System Type | Supply Air RH | Leaving Air Temp |
|---|---|---|
| Constant Volume | 85-95% | 52-55°F |
| VAV | 90-95% | 50-55°F |
| Dual Duct | 80-90% | Cold deck: 50°F Hot deck: 85-100°F |
| System | Primary Control | Reset Strategy |
|---|---|---|
| VAV | Duct static pressure | Reset based on zone demand |
| Chiller Plant | Supply water temp | Outdoor air reset |
| CAV | Discharge air temp | Night setback |