Comprehensive analysis of fire sprinkler system pressure and flow requirements
Technical Document
August 2023
Using pre-calculated tables for preliminary design stages
Detailed hydraulic calculations for accurate requirements
Refers to the instance when sprinklers at the hydraulically most unfavorable location activate.
Assumption: Pressure required for sprinkler discharge and pipe frictional losses downstream of alarm valve does not exceed 1.7 bar at minimum flow rate.
Refers to the instance when sprinklers at the hydraulically most favorable location activate.
Assumption: Pressure required for sprinkler discharge and pipe frictional losses downstream of alarm valve does not exceed 1.4 bar at maximum flow rate.
| Characteristic Point | Flow Rate (litres/min) | Pressure at Alarm Valve (bar) | Remarks |
|---|---|---|---|
| Point 1 (Most Unfavorable) | 1,100 | 6.271 | Design requirement (minimum flow rate) |
| Point 2 (Most Favorable) | 1,350 | 5.971 | Requirement at maximum demand |
The pump must be capable of providing these flow rates and pressures at the alarm valve ('C' gauge location).
Hydraulic calculations consider the AMAO - the maximum area where sprinklers are assumed to operate during a fire.
Standard: BS EN 12845:2004, Table 3
Determining the most unfavorable AMAO involves considering:
For this design, the most unfavorable AMAO includes sprinklers downstream of Design Point E at the 6th floor.
The AMAO should be as near as possible to rectangular shape, symmetrical with respect to sprinkler layout.
Actual AMAO shape determined by sprinkler coverage boundaries, resulting in a total area of 221.52 m² (>216 m² requirement).
| Parameter | Value | Standard Reference |
|---|---|---|
| Minimum Design Density | 5.0 mm/min (5.0 l/min/m²) | BS EN 12845:2004, Table 3 |
| Minimum Sprinkler Discharge Pressure | 0.35 bar | BS EN 12845:2004, Clause 13.4.4 |
| Maximum Flow Velocity (Pipes) | 10 m/s | BS EN 12845:2004, Clause 13.2.3 |
| Maximum Flow Velocity (Valves) | 6 m/s | |
| Calculation Method | Hazen-Williams formula (C=120) | BS EN 12845:2004, Clause 13.2.1 |
The relationship between pressure and flow rate for sprinklers is defined by:
Minimum flow rate calculation:
Complex hydraulic calculations were solved using the Newton-Raphson iterative method:
This method was implemented using custom functions in MS Excel for accurate and efficient calculations.
Custom functions were developed in Excel for:
The spreadsheet automated complex iterative calculations while allowing manual adjustment of key parameters.
Final results from hydraulic calculations:
These values exceed the minimum requirements specified in BS EN 12845:2004.
Minimum water volume: 185 m³
81 m³ (1,350 l/min × 60 min)
87 m³ (1,439 l/min × 60 min)
A reduced capacity tank can be used with sufficient inflow rate:
Requirement: City water supply must provide this inflow rate during peak demand periods.
| Parameter | Table Method | Hydraulic Calculation | Status |
|---|---|---|---|
| Flow Rate (l/min) | 1,350 | 1,439 | Adequate |
| Pressure at Alarm Valve (bar) | 5.971-6.271 | 6.528 | Adequate |
| Design Density (mm/min) | 5.0 | 5.574 | Exceeds Requirement |
| Water Storage (m³) | 81-185 | 87 | Adequate |