Fire Protection Plumbing Quick Reference Guide HVAC Cooling Load Analysis - Quick Reference

HVAC Cooling Load Analysis Reference Guide

1. Cooling Load Components

Main Sources of Heat Gain:

Source Examples
External Loads Sunlight, outdoor air temperature
Internal Loads People, lights, appliances
Infiltration/Ventilation Air leaks, fresh air intake

2. Required Data for Calculation

3. Calculation Methods

A. Manual Calculation (ASHRAE CLTD/CLF Method)

Conductive Heat Gain: Q = A × U × ΔT

Where: A = Area (m²), U = Heat transfer coefficient (W/m²K), ΔT = Temperature difference

Solar Heat Gain: Q = A × SHGC × SC × CLF
Internal Loads (People): Q = No. of People × Heat Gain (W/person)

B. Software-Based Calculation

4. Standards to Follow

International Standards:

Sri Lankan Standards (SLS):

5. Sri Lanka-Specific Considerations

6. Example Calculation (Small Office)

Load Type Calculation Heat Gain (W)
Wall Heat Gain 20m² × 2.5 W/m²K × (34°C-25°C) 450 W
Window Solar 10m² × 0.5 SHGC × 200 W/m² 1000 W
People (5) 5 × 70 W (sensible) + 5 × 60 W 650 W
Total Load Sum of all ≈1.1 TR

Add 15% safety factor → ~1.3 Tons Refrigeration (TR) Required