Fire Protection Plumbing Quick Reference Guide Sprinkler Standards Comparison: BS EN 12845 vs NFPA 13

Sprinkler Standards Comparison

BS EN 12845 vs NFPA 13

A comprehensive comparison of the two major fire sprinkler system standards used in Europe/UK and the United States.

Feature / Parameter BS EN 12845 (Europe / UK) NFPA 13 (USA) Key Differences / Notes
Hazard Classification OH (Ordinary Hazard) & EH (Extra Hazard), divided into groups I, II, III Light, Ordinary, Extra Hazard, divided into Groups 1 & 2 Terminology differs; BS uses numeric groups within OH/EH
Sprinkler Spacing (Center-to-Center) OH: 4.5–6 m; EH: 3–4.5 m Light: 4.6 m; Ordinary: 4.6–6.1 m; Extra Hazard: 3–4.6 m Maximum spacing values are similar; slight differences by hazard type
Coverage Area per Sprinkler OH: 20–36 m²; EH: 9–20 m² Light: 12–20 m²; Ordinary: 16–25 m²; Extra Hazard: 9–20 m² BS EN 12845 allows slightly larger coverage for certain OH areas
Water Density / Flow Rate Specified per hazard group (OH I-III, EH I-II) Specified per hazard classification (gpm/ft² or l/min/m²) Both specify density; units and calculation methods differ
Installation Type Wet pipe, dry pipe, pre-action, deluge Wet pipe, dry pipe, pre-action, deluge Similar system types; BS has some European-specific clauses
Obstruction / Wall Distance 0.5–0.75 m from walls or obstructions 0.15–0.46 m from walls depending on sprinkler type Narrower spacing near walls in NFPA 13
Maximum Height Between Sprinklers Up to 45 m for OH/EH, adjusted per group Typically 18–23 m per floor BS EN 12845 allows taller single-zone heights; NFPA 13 usually limits per story
Design Philosophy Prescriptive + performance guidance, hazard group tables Prescriptive, detailed tables for spacing, density, and coverage NFPA 13 has more detailed tables; BS EN 12845 is slightly more flexible for European buildings
Pipe Sizing Based on pressure loss calculations with specific k-factors Using pipe schedule or hydraulic calculation methods NFPA offers both prescriptive and calculative approaches; BS is more calculation-focused
Water Supply Duration 60-90 minutes depending on hazard classification 60-120 minutes depending on hazard classification NFPA generally requires longer water supply for high hazard occupancies

Click on any row to highlight it. Use the search box to filter specific parameters.