| Process | Direction | Key Change | Trane Example |
|---|---|---|---|
| Sensible Cooling | → Horizontal | DBT↓, W constant | Dry cooling coil |
| Cooling + Dehumid | ↙ Down-left | DBT↓, W↓ | Standard AC operation |
| Heating | → Horizontal | DBT↑, W constant | Furnace heating |
| Evaporative Cooling | ↖ Up-left | DBT↓, W↑ | Swamp cooler |
| SHF Range | Application | Trane Recommendation |
|---|---|---|
| 0.75-0.85 | Comfort cooling | Standard AC systems |
| 0.85-0.95 | Data centers | Precision cooling |
| 0.60-0.75 | High latent load | Dedicated dehumidification |
Trane's mixing rule: Mixed state lies on straight line between input states
| Factor | Effect | Trane Solution |
|---|---|---|
| High Face Velocity | ↑ Bypass, ↓ Dehumid | Reduce airflow or add rows |
| Low Refrigerant Temp | ↑ Condensation risk | Maintain >32°F coil temp |
| Dirty Coils | ↑ ΔP, ↓ Heat transfer | Regular cleaning |
| Symptom | Psychrometric Cause | Trane Recommendation |
|---|---|---|
| High RH, normal temp | Process line too flat | Check coil contact factor |
| Low RH, cold air | Excessive dehumid | Modulate reheat |
| Short cycling | Operating near ADP | Adjust setpoints |