HVAC Psychrometric Chart Practice Questions ASHRAE Fundamentals Key Points

ASHRAE Handbook Fundamentals - Critical Points

1. Thermal Comfort Standards (ASHRAE 55)
Parameter Winter Range Summer Range
Operative Temp (°F) 68-74 73-79
Relative Humidity (%) ≥30 ≤60
Air Speed (fpm) <50 <160

PMV-PPD Model: Acceptable PPD < 10% (PMV ±0.5)

2. Design Conditions
Condition Dry Bulb (°F) Wet Bulb (°F) Application
1% Cooling DB Location-specific - Peak load calc
0.4% Cooling DB/MCWB Higher than 1% Mean coincident Equipment sizing
99% Heating DB Location-specific - Heating systems
3. Heat Transfer Fundamentals
Q = U × A × ΔT
Material U-value (Btu/h·ft²·°F) R-value (ft²·°F·h/Btu)
Single pane glass 1.10 0.91
Insulated wall (R-13) 0.07 13.0
Roof (R-30) 0.03 30.0
4. Ventilation Requirements (ASHRAE 62.1)
Space Type Outdoor Air (cfm/person) Air Changes (ACH)
Office 5-17 0.3-0.6
Classroom 10-15 0.6-1.2
Retail 7.5-20 0.2-0.4

Ventilation Rate Procedure: Vot = Voz × Pz + Vbz × Az

5. Moisture Control Principles
Grains difference = 0.018 × (Pi - Po) × Rv
6. Load Calculation Essentials
Component Formula CLTD Values
Conduction Q = U × A × CLTD Table 18-12
Solar Gain Q = A × SC × SHGF × CLF Tables 15-17
Internal Loads Q = People + Lights + Equipment Tables 6-8
7. Psychrometric Chart Key Points