HVAC Psychrometric Chart Practice Questions
ASHRAE Fundamentals Key Points
ASHRAE Handbook Fundamentals - Critical Points
1. Thermal Comfort Standards (ASHRAE 55)
| Parameter |
Winter Range |
Summer Range |
| Operative Temp (°F) |
68-74 |
73-79 |
| Relative Humidity (%) |
≥30 |
≤60 |
| Air Speed (fpm) |
<50 |
<160 |
PMV-PPD Model: Acceptable PPD < 10% (PMV ±0.5)
2. Design Conditions
| Condition |
Dry Bulb (°F) |
Wet Bulb (°F) |
Application |
| 1% Cooling DB |
Location-specific |
- |
Peak load calc |
| 0.4% Cooling DB/MCWB |
Higher than 1% |
Mean coincident |
Equipment sizing |
| 99% Heating DB |
Location-specific |
- |
Heating systems |
3. Heat Transfer Fundamentals
Q = U × A × ΔT
| Material |
U-value (Btu/h·ft²·°F) |
R-value (ft²·°F·h/Btu) |
| Single pane glass |
1.10 |
0.91 |
| Insulated wall (R-13) |
0.07 |
13.0 |
| Roof (R-30) |
0.03 |
30.0 |
4. Ventilation Requirements (ASHRAE 62.1)
| Space Type |
Outdoor Air (cfm/person) |
Air Changes (ACH) |
| Office |
5-17 |
0.3-0.6 |
| Classroom |
10-15 |
0.6-1.2 |
| Retail |
7.5-20 |
0.2-0.4 |
Ventilation Rate Procedure: Vot = Voz × Pz + Vbz × Az
5. Moisture Control Principles
- Dew point must remain below surface temperatures
- Vapor retarder placement: Warm side in cold climates
- Permeance limits: <1 perm for vapor barriers
- Condensation risk when: Tsurface ≤ Tdewpoint
Grains difference = 0.018 × (Pi - Po) × Rv
6. Load Calculation Essentials
| Component |
Formula |
CLTD Values |
| Conduction |
Q = U × A × CLTD |
Table 18-12 |
| Solar Gain |
Q = A × SC × SHGF × CLF |
Tables 15-17 |
| Internal Loads |
Q = People + Lights + Equipment |
Tables 6-8 |
7. Psychrometric Chart Key Points
- Sensible heat ratio (SHR) = Qsen/Qtotal
- Apparatus dew point (ADP) determines coil performance
- Bypass factor: 0.1-0.3 for typical coils
- Standard air: 68°F DB, 50% RH, 0.075 lb/ft³